Page #17 background imageLoading...
Page #17 background image
17
© 2015 Emerson Climate Technologies, Inc.
AE4-1400 R1
Figure 3
Time Delay Wiring
C
Line Voltage
Typical Solid State Timer
(if used)
Discharge Line
Thermostat (if used)
Compressor Contactor
Other Protective
Devices (if used)
System Operating
Thermostat
Fuse
A
B
Ti
me Delay Relay Specifications
Ti
mer Opens: 1 Electrical Cycle Timer Closes: Greater than 5 seconds later, whether
(.016 Sec. With 60 HZ Operation) power is restored or not
after power is removed
Figure 4
Compressor Electrical Connection
T1,C
T2,S
T3,R