EasyManuals Logo
Home>Emerson>Controller>EXD-HP1

Emerson EXD-HP1 User Manual

Emerson EXD-HP1
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Operating instruction
EXD-HP1/2 Controller with ModBus
communication capability
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 17.12.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-HP12_OI_EN_DE_RU_1220_R06_865921.docx
General information:
EXD-HP1/2 are stand-alone superheat and or economizer controllers. EXD-HP1 is
intended for operation of one EXM/EXL or EXN valve whereas EXD-HP2 is
designed for operation of two independent EXM/EXL or two EXN valves.
Note: It is possible to use only circuit 1 from EXD-HP2. In this case, the circuit
2 must be disabled (C2 parameter) and the sensors and the valve for the second
circuit are not needed.
ModBus communication is described in a Technical Bulletin and it is not covered
by this document.
Technical Data:
Power supply
24VAC/DC ±10%; 1A
Power consumption
EXD-HP1: 15VA EXD-HP2: 20VA
Plug-in connector
Removable screw terminals wire size 0.14...1.5 mm
2
Protection class
IP20
Digital Inputs
Potential free contacts (free from voltage)
Temperature sensors
ECP-P30
Pressure sensors
PT5N
Operating/surrounding temp.
0…+55°C
Output alarm relay
SPDT contact 24V AC 1 Amp inductive load;
24V AC/DC 4 Amp resistive load
Activated/energized:
During normal operation (no alarm condition)
Deactivated/de-energized:
During alarm condition or power supply is OFF
Stepper motor output
Coil: EXM-125/EXL-125 or EXN-125
Valves: EXM/EXL-… or EXN-…
Type of action
1B
Rated impulse voltage
0.5kV
Pollution Degree
2
Mounting:
For standard DIN rail
Marking
Dimensions (mm)
Warning -Flammable refrigerants:
EXD-HP1/2 has a potential ignition source and does not comply with ATEX
requirements. Installation only in non-explosive environment. For flammable
refrigerants only use valves and accessories approved for it!
Safety instructions:
Read operating instructions thoroughly. Failure to comply can result in device
failure, system damage or personal injury.
It is intended for use by persons having the appropriate knowledge and skill.
Before installation or service disconnect all voltages from system and device.
Do not operate system before all cable connections are completed.
Do not apply voltage to the controller before completion of wiring.
Entire electrical connections have to comply with local regulations.
Inputs are not isolated, potential free contacts needed to be used.
Disposal: Electrical and electronic waste must NOT be disposed of with other
commercial waste. Instead, it is the user responsibility to pass it to a designated
collection point for the safe recycling of Waste Electrical and Electronic
Equipment (WEEE directive 2019/19/EU). For further information, contact
your local environmental recycling center.
Electrical connection and wiring:
Refer to the electrical wiring diagram for electrical connections.
Note: Keep controller and sensor wiring well separated from supply power
cables. Minimum recommended distance 30mm.
EXM-125, EXL-125 or EXN-125 coils are supplied with fix cable and JST terminal
block at cable end. Cut the wires close to terminal block. Remove the wire
insulation approximately 7 mm at the end. It is recommended that the wires end to
be equipped with core cable ends or metallic protective sleeve. When connecting
the wires of EXM/EXL or EXN, consider the color coding as follows:
EXD
Terminal
EXM/L-125 wire color
EXN-125 wire color
EXD-HP1
6 BR
7 BL
8 OR
9 YE
10 WH
Brown
Blue
Orange
Yellow
White
Red
Blue
Orange
Yellow
White
EXD-HP2
30 BR
31 BL
32 OR
33 YE
34 WH
Brown
Blue
Orange
Yellow
White
Red
Blue
Orange
Yellow
White
The digital input DI1 (EXD-HP1) and DI1/D12 (EXD-HP1/2) are the
interfaces between EXD-HP1/2 and upper level system controller if the
Modbus communication has not been used. The external digital shall be
operated in function system’s compressor/demand.
If the output relays are not utilized, the user must ensure appropriate safety
precautions are in place to protect the system.
Digital input status
closed (Start)
open (Stop)
Note: Connecting any EXD-HP1/2 inputs to the supply voltage will
permanently damage the EXD-HP1/2.
Wiring base board (EXD-HP1/2) :
Note:
Base board is for function of superheat control or Economizer control.
Alarm relay, dry contact. Relay coil is not energized during alarm condition or
power off.
Hot gas discharge sensor input is mandatory only for economizer control function.
Warning: Use a class II category transformer for 24VAC power supply. Do
not ground the 24VAC lines. We recommend using individual transformers for
EXD-HP1/2 controller and for third party controllers to avoid possible
interference or grounding problems in the power supply.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson EXD-HP1 and is the answer not in the manual?

Emerson EXD-HP1 Specifications

General IconGeneral
BrandEmerson
ModelEXD-HP1
CategoryController
LanguageEnglish

Related product manuals