GFK-2573AD May 2023
5
Status Reporting
The PNC001 provides 32 bits of status information to a configured location in the RX3i CPU’s reference
memory.
The status data consists of the Module OK bit, which indicates the health of the module itself, a status bit
for each external port, and a bit that indicates the connection status of the configured devices.
All Status bits are active high. The status location may be configured in %I, %Q, %AI, %AQ, %R, %G, %T, %M
or %W or I/O Variable reference memory in the RX3i CPU.
Name
Description
Module OK
Indicates the health of the PNC001 module.
1 indicates the module is functioning properly.
0 indicates the module is powering up or has failed.
Port1 Link Up
1 indicates the port is connected to another device and is operating correctly.
0 indicates the port is not connected to another device or the port has an error preventing
communications, or the SFP cage is empty or has an incompatible SFP device.
Port2 Link Up
Port3 Link Up
Port4 Link Up
Reserved
Reserved. Always 0.
Port3 SFP OK
Indicates the health of the SFP plugged in port 3.
1 indicates that the SFP matches the configuration and is operational.
0 indicates that either the SFP does not match the configuration or is not operational.
Port4 SFP OK
Indicates the health of the SFP plugged in port 4.
1 indicates that the SFP matches the configuration and is operational.
0 indicates that either the SFP does not match the configuration or is not operational.
All Devices
Connected
3
1 indicates all configured devices are connected and communicating over PROFINET.
0 indicates no devices are configured or one or more configured devices have not established
a PROFINET connection.
Reserved
Always 0.
MRP Enabled
0 indicates that MRP is not enabled.
1 indicates that MRP is enabled.
3
It is recommended that the All Devices Connected status bit be checked first to determine whether all devices belonging to the PNC001 are
functioning. If this bit is 0, indicating that one or more devices is not OK, the PNIO_DEV_COMM function block can then be used to determine
which specific devices are not communicating. For details on this status bit, refer to the section entitled Status Reporting in the RX3i
PROFINET I/O Controller Manual, GFK-2571.

Other manuals for Emerson PNC001-A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson PNC001-A Series and is the answer not in the manual?

Emerson PNC001-A Series Specifications

General IconGeneral
BrandEmerson
ModelPNC001-A Series
CategoryController
LanguageEnglish

Related product manuals