EasyManuals Logo

Endress+Hauser Liquicap M FTI51 User Manual

Endress+Hauser Liquicap M FTI51
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #83 background imageLoading...
Page #83 background image
Liquicap M FTI51, FTI52 Technical data
Endress+Hauser 83
10.5.3 Ambient temperature effect
Electronic insert
< 0.06 % / 10 K related to the full scale value
Separate housing
Capacitance change of connecting cable per meter 0.15 pF/10K
10.6 Operating conditions: Environment
10.6.1 Ambient temperature range
Ambient temperature of the transmitter (note derating, see Page 85 ff.):
–50 to +70 °C
–40 to +70 °C (with F16 housing)
A weather protection cover should be used when operating outdoors in strong sunlight. For
further information on the weather protection cover, see Page 76.
10.6.2 Storage temperature
–50 °C to +85 °C
10.6.3 Climate class
DIN EN 60068-2-38/IEC 68-2-38: test Z/AD
10.6.4 Degree of protection
* As per EN60529
** As per NEMA 250
10.6.5 Vibration resistance
DIN EN 60068-2-64/IEC 68-2-64: 20 Hz– 2000 Hz; 0.01 g
2
/Hz
10.6.6 Cleaning
Housing:
When cleaning, make sure that the cleaning agent used does not corrode the housing surface or the
seals.
IP66* IP67* IP68* NEMA4X**
Polyester housing F16 X X - X
Stainless steel housing F15 X X - X
Aluminum housing F17 X X - X
Aluminum housing F13
with gas-tight process seal
X–XX
Aluminum housing T13
with gas-tight process seal and separate
connection compartment (EEx d)
X–XX
Separate housing X X X

Table of Contents

Other manuals for Endress+Hauser Liquicap M FTI51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Liquicap M FTI51 and is the answer not in the manual?

Endress+Hauser Liquicap M FTI51 Specifications

General IconGeneral
BrandEndress+Hauser
ModelLiquicap M FTI51
CategorySwitch
LanguageEnglish

Related product manuals