950N 12 732773 - Rev. B
ENGLISH
ITALIANO
• 1 LANGUAGE (Diagram 2)
Selects the language in which the messages are displayed.
• 2 SETUP (Diagram 3) -
• 2.1 PARTIAL OPENING
Partial opening percentage
Selects the opening percentage (with reference to total
opening) obtained when in “Partial Opening” mode.
Standard value: 80%
Adjustment: from 60% to 100%
• 2.2 PAUSE TIME
Pause time value
Sets the pause time in automatic operating modes.
Standard value: 2 sec.
Adjustment: from 0 to 30 sec.
• 2.3 NIGHT PAUSE TIME
Night pause time value
Sets the pause time in “night” operating mode.
Standard value: 7 sec.
Adjustment: from 0 to 30 sec.
• 2.4 OBSTACLE DETECTION
Determines the behaviour of the automated system in case
of repeated obstacle detection during the same operation.
Standard: The automated system attempts to complete
the operation.
No Standard: Following the detection of an obstacle for
three consecutive times, the automated system stops. Once
the obstacle has been removed, the door must be closed
manually to restore normal operation
• 3 LOCK (Diagram 4)
• 3.1 LOCK KIT
On: Lock installed
Night: The electric lock locks the door only in “Night” mode.
One-Way+Night: The electric lock locks the door in “Night”
and “One-way” mode.
Always: The electric lock locks the door every time it closes,
regardless of the set operating mode.
Off: Lock not installed.
• 4 DIAGNOSTICS (Diagram 5)
• 4.1 950
Shows the port hardware model and the software version
of the 950 MPS and 950 I/O boards to which the KP-
CONTROLLER is connected.
• 4.2 Nr. of CYCLES
Shows the count (not resettable) of the cycles performed
by the automated system.
• 4.3 FAULT Nr.
Shows the number and description of the fault in progress.
Refer to gure 3 for fault codes and descriptions.
• RESET
Performs the reset procedure and, if the cause of the
previously signalled fault has been eliminated, it restores
normal operation.
• 5 ADVANCED MENU
• PASSWORD
To access the advanced menu, the 4-digit password is
required (default 0000).
• 1 MOTION PARAMETERS (Diagram 6)
• 1.1 CLOSING SPEED
Sets the door speed during closing.
Standard value: level 8
Adjustment: from 0 to 10
• 1.2 OPENING SPEED
Sets the door speed during opening.
Standard value: level 8
Adjustment: from 0 to 10
• 1.3 MAINTAIN SETTINGS
On: The automated system maintains the operating
parameters set using the KP-CONTROLLER even if the
latter is disconnected
Off: If the KP-CONTROLLER is disconnected, the opening
and closing speed and the pause time must be set using
the trimmers.
• 2 IN/OUT SETUP (Diagram 7)
• 2.1 EMERG
Sets the effect of the emergency command
(Emerg input on the 950 I/O board).
Standard setting: Opens/NC
Opens: Activating the command opens the door.
Closes: Activating the command closes the door.
No: Normally open input.
Nc: Normally closed input.
• 2.2 OUT OP/CL
Sets operation of the Open and Closed status outputs of
the 950 I/O board.
Standard setting: N.O.
Nc: Normally closed output.
No: Normally open output
• 2.3 FAULT OUT
Sets operation of the Fault status outputs of the 950 I/O
board.
Standard setting: N.O.
No: Normally open output.
Nc: Normally closed output.
• 3 OTHER (Diagram 8)
• 3.1 STANDARD SET UP
Makes it possible to verify if any non-standard programming
has been performed.
Standard: If no standard programming function has been
modied, an asterisk will be displayed. If the asterisk
is not displayed, press “OK” to restore all the standard
programming settings.
No Standard: If at least one standard programming function
has been modied, an asterisk will be displayed.
• 3.2 INTERLOCK
The interlock function makes it possible to manage two
doors (master and slave) so that opening of one depends
on the closing of the other and vice versa.
Off: Interlock not active
On: Interlock active.
7.1 DIAGRAM DESCRIPTION