FLUID COMPONENTS INTERNATIONAL LLC FLT93 Flow Switch Series
This page is subject to proprietary rights statement on last page
4 Doc. No. 06EN003312 Rev. D
Jumper Placement
Input Power
Relay Energization
Selectable Heater Wattage Control
Jumper Locations (Underlined Jumpers are default)
Relay Contact Configuration
Standard Default Jumper Configuration
J22 SINGLE SPDT (DISABLES ALARM NO. 2)
J23
DUA L DPDT (ONE RELA Y PER A LA RM)
100-130 VAC 200-260 VAC 21-30 VDC 18-26 VAC
J1 IN OUT OUT OUT
J2 OUT IN OUT OUT
J3 IN OUT OUT OUT
J4 OUT OUT OUT IN
J5 IN IN OUT OUT
J6 OUT IN IN IN
J7 OUT OUT IN OUT
J8 OUT OUT IN OUT
J9 OUT OUT OUT IN
POWER SELECT
JUM PER
FLOW / LEVEL TEM P
ALARM NO. 1 J20
J21
ALARM NO.2 J18 J19
JUM PER J32 J12 J13* J14* J33
FLT93-F ELEMENT
WATTAGE (560 OHM HTR)
FL T9 3- S ELEMENT
WATTAGE (110 OHM HTR)
0.57
WA TTS
0.52
WA TTS
3
WA TTS
1.75
WA TTS
*J13 IS STA NDA RD FOR FLT-S A ND J14 IS STA NDA RD FOR FLT93-F.
0.75
WA TTS
0.21
WATTS
OFF
OFF
0.49
WA TTS
0.25
WATTS
JUMPER ALARM NO. 1
RELA Y DE-ENERGIZED WITH LOW FLOW,
LOW LEVEL (DRY) OR HIGH TEMPERATURE.
RELA Y DE-ENERGIZED WITH HIGH FLOW,
HIGH L EV EL ( W ET) OR L OW TEMPERA TURE.
ALARM NO. 2
RELA Y DE-ENERGIZED WITH LOW FLOW,
LOW LEVEL (DRY) OR HIGH TEMPERATURE.
RELA Y DE-ENERGIZED WITH HIGH FLOW,
HIGH L EV EL ( W ET) OR L OW TEMPERA TURE.
J27
J26
J25
J24
INPUT POWER
FLT93-S 0.75 WA TTS FOR A IR OR LIQUID A PPLICA TIONS (J13)
FLT93- F 0.25 WA TTS FOR A IR OR LIQUID A PPLICATIONS (J14)
NUMBER OF A L A RMS
230 VAC (J2, J5 AND J6), OR FM APPROVAL 120 VAC (J1, J3, J5)
SET TO MONITOR FLOW OR LEVEL SIGNALS (J20).
RELAY ENERGIZED BELOW TEMPERATURE (J25)
SET POINT AT APPROXIMATELY:
250°F (121°C) FOR STANDARD TEMPERATURE,
500°F (260°C) FOR MEDIUM TEMPERATURE,
850°F (454°C) FOR HIGH TEMPERATURE (FLT93-S ONLY).
HEA TER POWER
ALARM NO. 1 RED LED
SET POINT POT R26
ALARM NO. 2 GREEN LED
SET POINT POT R25
SET TO MONITOR FLOW OR LEVEL SIGNALS (J20).
RELA Y ENERGIZED AT FLOW OR WET (J27)
TWO ( J23). EA CH A LA RM HA S ONE SET OF SPDT CONTA CTS.
Alarm Application