Instruction Manual Supplement
D104328X012
DVC6200 Digital Valve Controller
February 2018
2
475 Field Communicator and AMS Trex Device Communicator
1. If using the 475 Field Communicator, Select the HART Icon from the Main Menu, shown in figure 1.
If using the Trex Communicator, select Field Communicator from the main menu.
Figure 1. 475 Field Communicator Menu Screen
2. From the Online menu select Configure > Guided Setup > Device Setup.
3. Provide the requested information, including: Pressure Units, Relay Type, Control mode (Travel Control, Pressure
Control, Fallback-Sensor Failure, Fallback-Sensor/Tvl Deviation), max supply pressure, Actuator manufacturer,
Actuator model, Actuator size, Volume Booster/Quick Release.
4. Send the configuration to the instrument.
5. Use factory defaults for setup
6. Select Cancel (475) or Abort (Trex) when prompted to run Auto Tvl Calib.
7. Place the instrument “In Service”.
ValveLink Mobile
AMS Trex Device Communicator or 475 Field Communicator
1. Select ValveLink Mobile from the Field Communicator Main Menu (see figure 1).
2. Select HART device.
3. Select Connect from the ValveLink Mobile main menu (see figure 2) to connect to the instrument.
4. Select Setup > Setup Wizard.
5. Provide the requested information then select Apply.
6. When prompted to run an Auto Travel Calibration select No.
7. Place the instrument “In Service”.