Recoil start
13
OPERATION
Grounding the Generator
To avoid electrocution, this generator must be properly grounded prior to use. For instructions see Control Panel Functions
pg. 10.
Standard Atmospheric Conditions
Ambient Temperature: 77ºF (25ºC)
Barometric Pressure: 100kPa
Relative Humidity: 30%
Generator output will vary due to changes in temperature, altitude, and humidity. If the temperature, humidity, or altitude are
higher than standard atmospheric conditions, the generator’s output will be reduced. The load attached to the generator must
therefore be reduced.
How to Start Engine
OFF
ON
ON
OFF
Economy switch
Fuel valve switch
• Place generator on a level surface. All electrical loads MUST be disconnected from generator.
• Turn the Economy switch to “OFF” position.
• Turn the Fuel valve to "on" position.
For recoil start
Pull recoil handle (starter cord) slowly until resistance is felt, then pull rapidly.
1. Check oil level.
2. Battery must be connected for auto choke to work.
3. Make sure the circuit breakers are properly set.
4. Confirm that the Fuel valve Switch is in the ON position.
5. Push the START button on the panel.
For one push start