22 – AUTOMATIC HUMIDITY CONTROL
00 Disable automatic humidity control;
01 * Enable automatic humidity control;
When “Automatic Humidity Control” is enabled
, thermostat will turn on
air conditioning in an unoccupied room when humidity raises above
60% and room temperature is above 72°F until either room humidity
is below 55% or room temperature is below 72°F
;
* Indicates default setting;
This setting is active only on thermostats with enabled humidity
features. Changing this setting on a non-humidity thermostat will have
no effect on thermostat operation.
Humidity features can be enabled on compatible thermostats via
online management.
Certain models only. Additional fees apply.