At the time when the air conditioner is switched from the Cooling mode to Heating mode,
the compressor is stopped, and the 4-way valve is switched in 3 minutes later
after the compressor stopped.
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically resumed with
the memorized operation contents.
(Table 8 : Operation contents memorized when the power is interrupted)
Operation mode
Set temperature
Set air flow
Thermistor detected position
11. 4-WAY VALVE EXTENSION SELECT
12. AUTO RESTART
01-23
13. MANUAL AUTO OPERATION
If MANUAL / AUTO Button is pushed continuous from 3 seconds to 10 seconds,
manual auto operation will starts.
If the remote control is lost or battery power dissipated, this function will work without the remote
control.
OPERATION MODE
Auto changeover
Auto
Continuous
(No timer setting available)
24°C
(Table 9 : Manual auto operation control)
SETTING TEMP.
FAN MODE
TIMER MODE
Timer mode
Wireless remote controller
Wired remote controller
(When Memory Backup : Disable)
Wired remote controller
(When Memory Backup : Enable)
OFF Timer
ON Timer
WEEKLY Timer
Temperature
: Memorize
: Not memorize
*It is necessary to set on the DIP-SW1-No,6 of the wired remote controller, to enable the memory backup.
Refer to the installation manual of wired remote controller for details.
SWING OPERATION
ECONOMY
OFF
OFF
VERTICAL LOUVER
NORMAL
NORMAL
HORIZONTAL LOUVER
All models
Functions
SET BACK Timer