14. COMPRESSOR PREHEATING
01-24
When the outdoor heat exchanger temperature is lower than Operation temperature (Refer to Table 10)
and the heating operation has
been stopped for 3 hours, power is applied to the compressor and
the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor temperature rises to Release temperature or greater,
preheating
is over.
(Table 10 : Preheating Operation / Release Temperature)
Before 24 hour After 24 hour
Operation
temperature
Operation
temperature
Release
temperature
Release
temperature
3°C 7°C 0°C 4°C
15. POWERFUL OPERATION
The POWERFUL OPERATION functions by pressing POWERFUL button on the remote controller.
The indoor unit & outdoor unit will operate at maximum power as shown in Table11.
Release Condition is as follows.
[Cooling / Dry]
- Room tenperature < Setting temperature - 1.5°C or Operation time has passed 20 minutes.
COMPRESSOR FREQUENCY Maximum
FAN CONT. MODE Powerful
SETTING LOUVER Cooling/ Dry : 3, Heating : 5
(Table11)
Powerful operation
=
=
[Heating]
- Room tenperature > Setting temperature +1.5°C or Operation time has passed 20 minutes.
16. 10°C HEAT OPERATION
10°C HEAT operation performs as below when pressing 10°C HEAT button or
Weekly timer setting on the remote controller.
Mode Heating
Setting temperature 10°C
Fan mode Auto
LED display Economy
Defrost operation Operate as normal
(Table 12 : 10°C HEAT operation )
17. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller.
At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation
for cooling and heating.
The ECONOMY operation is almost the same operation as below settings.
Mode Cooling/ Dry Heating
Target temperature Setting temp.+1°C Setting temp.-1°C
(Table 13 )