7. Additional charge calculation
7-1. Model: AOYG18KBTB
Refrigerant type R32
Refrigerant amount g 1,020
¢ Refrigerant charge
Total pipe length m 20 or less 25 30 (Max.)
20 g/m
Additional charge g 0 100 200
7-2. Models: AOYG22KBTB and AOYG24KBTB
Refrigerant type R32
Refrigerant amount g 1,250
¢ Refrigerant charge
Total pipe length m 20 or less 25 30 (Max.)
20 g/m
Additional charge g 0 100 200
7-3. Models: AOYG30KBTB and AOYG36KBTB
Refrigerant type R32
Refrigerant amount g 1,900
¢ Refrigerant charge
Total pipe length m 30 or less 40 50 (Max.)
40 g/m
Additional charge amount g 0 400 800
7-4. Model: AOYG45KBTB
Refrigerant type R32
Refrigerant amount g 2,700
¢ Refrigerant charge
Total pipe length m 30 or less 40 50 (Max.)
40 g/m
Additional charge amount g 0 400 800
- 88 -
7-1. Model: AOYG18KBTB 7. Additional charge calculation
OUTDOOR UNIT
AOYG18-45KBTB
OUTDOOR UNIT
AOYG18-45KBTB

Table of Contents

Other manuals for Fujitsu ARXG12KHTAP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG12KHTAP and is the answer not in the manual?

Fujitsu ARXG12KHTAP Specifications

General IconGeneral
BrandFujitsu
ModelARXG12KHTAP
CategoryAir Conditioner
LanguageEnglish

Related product manuals