2-41. E: A8. Refrigerant leakage sensor error (Indoor unit)
Indicator Indoor unit
Operation indicator 10 time flash
Timer indicator 8 time flash
Economy indicator Continuous flash
Error code E: A8
Detective actuator Refrigerant leakage sensor
Forecast of cause Refrigerant leakage
Check point 1. Refrigerant leakage detection conditions
When the refrigerant leakage sensor detects refrigerant.
System stop -> Cooling/heating cannot be operated.
Stir operation by fan -> Safety is important, and fan operation cannot be stopped.
-> Check for refrigerant leaks and take corrective action.
Check point 2. Error release condition
Power on again.
If the power is not turned on again, the error will not be cleared even if the gas concentration
drops.
If the refrigerant leakage is detected again after the power is turned on again, an error will occur
again.
Replace the refrigerant leakage sensor as it will not recover if exposed to a high concentration
of gas or if exposed multiple times even if the concentration is not high.
End
2-41. E: A8. Refrigerant leakage sensor error (Indoor unit) - (03-57) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ARXG14KSLAP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG14KSLAP and is the answer not in the manual?

Fujitsu ARXG14KSLAP Specifications

General IconGeneral
BrandFujitsu
ModelARXG14KSLAP
CategoryAir Conditioner
LanguageEnglish

Related product manuals