6-1. Defrost operation in heating operation stopped
If the outdoor unit is frosted when stopping the heating operation, it stops after performing the auto-
matic defrosting operation.
In this time, if the indoor unit operation lamp flashes slowly (6 sec on/2 sec off), the outdoor unit al-
low the heat exchanger to defrost, and then stop.
Triggering condition
When all of the following conditions are satisfied in heating operation
Compressor operation integrating time: 30 minutes or more
Compressor continuous operation time: 10 minutes or more
Outdoor unit heat exchanger temperature: -4°C or less
Release condition
The defrost operation is released when either one of the conditions below is satisfied.
Outdoor unit heat exchanger temperature
(after 1 minute or later since compressor start)
12°C or more
Compressor operation time 15 minutes
6-1. Defrost operation in heating operation stopped - (04-28) - 6. Defrost operation control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Other manuals for Fujitsu ARXG24KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG24KMLA and is the answer not in the manual?

Fujitsu ARXG24KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG24KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals