6-2. Model: AOYG30KATA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.926
20 0.953 0.942
10 0.979 0.968 0.958
7.5 0.988 0.983 0.972 0.961
5 0.992 0.992 0.987 0.976 0.965
0 1.000 1.000 0.995 0.984 0.973
Indoor unit is lower
than outdoor unit *2
-5 1.000 1.000 0.995 0.984 0.973
-7.5 1.000 0.995 0.984 0.973
-10 0.995 0.984 0.973
-20 0.984 0.973
-30 0.973
HEATING
Pipe length (m)
5 7.5 10 20 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.931
20 0.954 0.931
10 0.990 0.954 0.931
7.5 1.000 0.990 0.954 0.931
5 1.000 1.000 0.990 0.954 0.931
0 1.000 1.000 0.990 0.954 0.931
Indoor unit is lower
than outdoor unit *2
-5 0.995 0.995 0.986 0.949 0.926
-7.5 0.993 0.983 0.946 0.924
-10 0.981 0.944 0.921
-20 0.935 0.912
-30 0.903
- 86 -
6-2. Model: AOYG30KATA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG24-45KATA
OUTDOOR UNIT
AOYG24-45KATA

Table of Contents

Other manuals for Fujitsu ARXG30KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG30KMLA and is the answer not in the manual?

Fujitsu ARXG30KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG30KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals