6-3. Model: AOYG36KATA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 — — — — 0.902
20 — — — 0.938 0.917
10 — — 0.973 0.953 0.933
7.5 — 0.988 0.977 0.957 0.936
5 0.992 0.992 0.981 0.961 0.940
0 1.000 1.000 0.989 0.968 0.947
Indoor unit is lower
than outdoor unit *2
-5 1.000 1.000 0.989 0.968 0.947
-7.5 — 1.000 0.989 0.968 0.947
-10 — — 0.989 0.968 0.947
-20 — — — 0.968 0.947
-30 — — — — 0.947
HEATING
Pipe length (m)
5 7.5 10 20 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 — — — — 0.978
20 — — — 0.988 0.978
10 — — 0.998 0.988 0.978
7.5 — 1.000 0.998 0.988 0.978
5 1.000 1.000 0.998 0.988 0.978
0 1.000 1.000 0.998 0.988 0.978
Indoor unit is lower
than outdoor unit *2
-5 0.995 0.995 0.993 0.983 0.973
-7.5 — 0.993 0.991 0.981 0.971
-10 — — 0.988 0.978 0.968
-20 — — — 0.968 0.958
-30 — — — — 0.949
- 87 -
6-3. Model: AOYG36KATA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG24-45KATA
OUTDOOR UNIT
AOYG24-45KATA