01-11
The compressor won't enter operation status for 2 minutes and 20 seconds after the compressor is stopped,
even if any operation is given.
At the time when the air conditioner is switched from the cooling mode to heating mode, the
compressor is stopped, and the four-way valve is switched in 2 minutes and 20 seconds later after
the compressor stopped.
11. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
12. FOUR-WAY VALVE EXTENSION SELECT
10. TEST OPERATION CONTROL
Under the condition where the air conditioner runs, press the TEST RUN button, and
the test operation control mode will appear.
During test running, the Operation lamp and Timer lamp of the air conditioner body twinkle simultaneously.
Set the test operation mode, and the compressor will continue to run regardless of whether the room
temperature sensor detects.
The test operation mode is released if 60 minutes have passed after setting up the test operation.
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically started with
the memorized operation contents.
When the power is interrupted and recovered during timer operation, since the timer operation time
is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF)
the indoor unit body Timer lamp.
[ Operation contents memorized when the power is interrupted ]
Operation mode
Set temperature
Set air flow
Timer mode and set time
Set air flow Direction
Swing
ECONOMY operation
13. AUTO RESTART
14. MANUAL AUTO OPERATION (Indoor unit body operation)
When the remote control is lost or battery power dissipated, this function will work without the remote control.
When MANUAL AUTO button is set more than 3seconds and less than 10seconds, MANUAL AUTO OPERATION
will be started as shown in Table14.
To stop operation, press the MANUAL AUTO button for 3seconds.
(Table14 : MANUAL AUTO OPERATION)
Press and hold MANUAL AUTO
button for 3 ~ 10seconds
OPERATION MODE Auto changeover
FAN CONT. MODE Auto
TIMER MODE Continuous
SETTING TEMP. 24°C
SETTING LOUVER Standard
SWING
ECONOMY
OFF
OFF
(No timer setting available)
Manual auto operation

Other manuals for Fujitsu ASYG07LLCE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG07LLCE and is the answer not in the manual?

Fujitsu ASYG07LLCE Specifications

General IconGeneral
BrandFujitsu
ModelASYG07LLCE
CategoryAir Conditioner
LanguageEnglish

Related product manuals