5. INDOOR FAN CONTROL
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs.
When fan mode is set at [Auto], it operates on [Me] fan Speed.
01-04
2. FAN OPERATION
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Figure4.
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Cool]
operation modes Quiet, Lo, Me, Hi, as shown in Table 6.
( Fig.4 : Airflow change - over ( Cooling : Auto ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > 2°C
1°C > TR-Ts
2°C > TR-Ts > 1°C
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C
=
Hi mode
Me mode
Lo mode
1. Fan speed
( Table 6 : Indoor fan speed )
Operation mode Air flow mode
Speed (rpm)
Cooling/ Fan
Heating
Dry
X zone: 700
J zone: 600
X zone: 700
J zone: 600
Model 07/ 09
Model 12
4. DRY OPERATION
Refer to the Table 6.
During the dry mode operation, the fan speed setting can not be changed.
Hi
Hi
Me+
Me
Me
Lo
Lo
Quiet
* Soft Quiet
Quiet
S-Lo
Cool air prevention
Powerful
Powerful
1420
1360
1290
1120
900
700
600
480
1400
1320
1120
840
700
600
1420
1360
1290
1120
900
700
600
480
1400
1320
1120
860
700
600
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)