EasyManuals Logo
Home>Fujitsu>Air Conditioner>AUXG07KVLA

Fujitsu AUXG07KVLA User Manual

Fujitsu AUXG07KVLA
403 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #290 background imageLoading...
Page #290 background image
3. Fan control
Tr: Room temperature
Ts: Setting temperature
3-1. Indoor fan control
¢ Compact cassette type
Fan speed
Indoor fan speed is defined as below.
Operation mode Fan mode
Speed (rpm)
AUXG07KVLA AUXG09KVLA AUXG12KVLA AUXG14KVLA
Heating
HIGH 590 590 650 830
MED+ 570 570 620 770
MED 540 540 580 730
LOW 490 490 520 630
QUIET 440 440 460 500
Cool air
prevention
400 400 400 400
S-LOW 300 300 300 300
Cooling/Fan
HIGH 590 590 650 730
MED 540 540 580 630
LOW 490 490 520 540
QUIET 440 440 460 460
Soft quiet
400*
1
400*
1
400*
1
400*
1
S-LOW
300*
2
300*
2
300*
2
300*
2
Dry
X zone: 440
J zone: 440
X zone: 440
J zone: 440
X zone: 460
J zone: 460
X zone: 460
J zone: 460
*1: Fan mode only
*2: Cooling mode only
Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH while indoor unit fan
only runs.
When fan mode is set at AUTO, it operates on MED fan speed.
3-1. Indoor fan control
- (04-28) - 3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Other manuals for Fujitsu AUXG07KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG07KVLA and is the answer not in the manual?

Fujitsu AUXG07KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG07KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals