1-6. Wired remote controller (UTY-RNNGM)
DIP switch 1
SW1 Prohibited
SW2 Dual remote controller setting
SW3 Prohibited
SW4 °F/°C switch
SW5 Prohibited
SW6 Memory backup setting
* Do not use DIP switch 2.
¢
Switch location
1
2
3
4
5
6
Front case (back side)
DIP switch 2
DIP switch 1
ONOFF
¢
DIP switch 1 setting
SW2: Dual remote controller setting
Set the remote controller SW2 according to the following table.
Number of remote controller
Primary unit Secondary unit
Factory setting
SW2 SW2
1 (Normal) OFF
2 (Dual) OFF ON
1 2 31 2 3
1 2 3
Indoor unit
Remote controller cable
Primary unit
Secondary
unit
Remote controller
SW4: Switching temperature unit °F / °C
Displayed temperature unit can be switched between Fahrenheit (°F) and Celsius (°C).
SW4 Fahrenheit (°F) / Celsius (°C) Factory setting
OFF °C
ON °F
1-6. Wired remote controller (UTY-RNNGM) - (05-47) - 1. Function settings (for indoor unit)
FIELD
WORKING
FIELD
WORKING

Table of Contents

Other manuals for Fujitsu AUXG07KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG07KVLA and is the answer not in the manual?

Fujitsu AUXG07KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG07KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals