modications reserved 8 User manual ML Series 350-1000 VA UPS 1.0 (GB)
5 - MAINTENANCE
5.1 General
The UPS is virtually maintenance free: take care of proper environmental conditions and keep air inlets-
outlets free of dust. Please read 2.1.
5.2 Fuses
If the AC input fuse (1) is defective, be sure it is replaced by a compatible fuse from the same make and
type. Fuse ratings: see chapter 7.
5.3 Batteries
5.3.1 General
The service life of the battery is up to 6 years.
As a healthy battery is critical to the UPS, keypad ‘ON’ allows a battery test (3.2.2). When the condition of
the battery is critical, a ‘replace battery’ alarm will be given (see 3.3). Charge the batteries for at least 10
hours, switch the UPS off and back on, and perform a self test. If the alarm persists replace the batteries as
soon as possible.
5.3.2 Battery replacement
• Warning: rst read the safety rules in section 1.2.
• When replacing the batteries, use the same number and voltage(V)/capacity(Ah).
• Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal
requirements.
• Never dispose of batteries in a re: they may explode.
• Do not open or mutilate batteries: their contents (electrolyte) may be extremely toxic. If exposed to
electrolyte, wash immediately with plenty of water.
• Avoid charging in a sealed container.
• Never short circuit batteries. When working with batteries, remove watches, rings or other metal objects,
and only use insulated tools.
Battery replacement procedure (ML 350/500/700)
NOTE: This procedure refers to the ML 350/500/700 models only. The batteries of the ML 1000 are not user
replaceable, please contact your dealer.
1 press keypad “OFF’ and remove the UPS input power cord from the AC mains supply
2 remove UPS front panel (two screws on bottom side)
3 pull out the battery and disconnect the battery wires
4 connect the new battery (black -, red +); small sparks can occur, this is normal
5 reinstall the new battery, do not pinch or clamp the wires
6 reinstall UPS front panel.

Other manuals for GE Digital Energy

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Digital Energy and is the answer not in the manual?

GE Digital Energy Specifications

ML Series model 350

Power IconPower
voltage amperes350 VA
watts210 W
ac input voltage220 - 240 Vac
maximum ac input voltage350 Vac
minimum start-up ac voltage150 Vac
input frequency50 Hz
typical no-load power consumption12 W
Battery IconBattery
nominal voltage12 Vdc
number x capacity of batteries1x5 Ah
recharge current0.5 A
battery recharge time for 80% capacity3 hours
Weight and Dimensions IconWeight and Dimensions
weight6.5 kg
dimensions150x110x300 mm

ML Series model 500

Power IconPower
voltage amperes500 VA
watts300 W
ac input voltage220 - 240 Vac
maximum ac input voltage350 Vac
minimum start-up ac voltage150 Vac
input frequency50 Hz
typical no-load power consumption12 W
Battery IconBattery
nominal voltage12 Vdc
number x capacity of batteries1x7 Ah
recharge current0.7 A
battery recharge time for 80% capacity3 hours
Weight and Dimensions IconWeight and Dimensions
weight7.5 kg
dimensions150x110x300 mm

ML Series model 700

Power IconPower
voltage amperes700 VA
watts420 W
ac input voltage220 - 240 Vac
maximum ac input voltage350 Vac
minimum start-up ac voltage150 Vac
input frequency50 Hz
typical no-load power consumption27 W
Battery IconBattery
nominal voltage24 Vdc
number x capacity of batteries2x5 Ah
recharge current0.5 A
battery recharge time for 80% capacity3 hours
Weight and Dimensions IconWeight and Dimensions
weight11 kg
dimensions150x110x420 mm

ML Series model 1000

Power IconPower
voltage amperes1000 VA
watts600 W
ac input voltage220 - 240 Vac
maximum ac input voltage350 Vac
minimum start-up ac voltage170 Vac
input frequency50 Hz
typical no-load power consumption27 W
Battery IconBattery
nominal voltage24 Vdc
number x capacity of batteries2x7 Ah
recharge current0.7 A
battery recharge time for 80% capacity3 hours
Weight and Dimensions IconWeight and Dimensions
weight13 kg
dimensions150x110x450 mm