Page #24 background image
modifications reserved
OPM_VHE_XXX_0K7_3K0_XGB_V010
23 User manual VH Series 700-3000 UPS 1.0 (GB)
9 - Specifications
VH Series : 700 1000 1500 2000 3000
Ratings
Voltage Amperes (VA) with computer type load : 700 1000 1500 2000 3000
Watts (W) with resistive load : 490 700 1050 1400 2100
Input thermal circuit breaker (A) : 7 7 8 10 16
Internal input fuse 250V, slow (A) : 8 8 10 16 20
Input converter
AC input voltage : 220 - 240 V
AC input voltage range : 100% load: 160 - 280 V
70% load: 130 - 280 V
input >280 Vac: UPS switches to battery operation
Minimum start-up AC voltage : 170 V (at any load)
Input current waveform : sinusoidal, conform or better than EN 61000-3-2 (IEC 555-2)
Input current (A) at nom. inp. volt. : 3.0 4.4 6.4 8.8 11.1
Input power factor : 1
Input frequency range : 45 - 66 Hz
Inrush current : none
Output converter
AC output voltage : 220 / 230 / 240 V (selectable)
AC output voltage tolerance : ± 2%
Output frequency : 50 or 60 Hz, front selectable
Output frequency range : nominal ± 0.15% unless synchronized to the mains
Output waveform : sine wave
Harmonic distortion : < 2% (typical 1%) with linear load
Power factor : 0.7
Crest factor (peak to RMS current) : suitable for loads with c.f. up to 6:1
Capacity appliance outlets : max. 10 A per outlet (one 16A outlet on VH Series 3000 VA)
Bypass
AC input voltage range : selected output voltage +15% -10%
Frequency tracking rate : 2 Hz/sec.
Frequency tracking range : nominal ± 10%
Phase difference : < 7º
Typical transfer time, msec : 1
Overload capability : fully protected against overload and short circuits
Overload behaviour during battery operation : 110% during 5 minutes
: 150% during 5 seconds
Overload behaviour during bypass operation : depends on rating of thermal circuit breaker
typical: 125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc) : 36 36 36 72 72
Number / Ah batteries : 3 / 7 3 / 7 3 / 9 6 / 7 6 / 9
Type : sealed lead acid, maintenance free
Service life : up to 6 years (depending on use)
Recharge current : 1.7 A
Battery recharge time
(batt. discharged at 100% load) : 1.5 hours for 90% capacity, std battery
Runtime in minutes
at typical load (75%) : 16 11 8 11 8
VA/Watts
100/70 : 120 120 180 >180 >180
300/210 : 32 32 40 60 75
700/490 : 13 13 16 30 35
1000/700 : - 8 10 20 20
1500/1050 : - - 6 11 16
2000/1400 : - - - 8 10
3000/2100 : - - - - 6
General
Weight UPS (kg) : 18.3 18.3 19.3 31.1 33.1
Dimensions UPS (hxwxd, tower orientation) : 440x87x472mm 440x87x547mm
Weight 14Ah battery pack 36Vdc / 72V (kg) : 29 / 47
Dims batt pack 36Vdc/72Vdc (hxwxd, tower orientation) : 440x87x472mm / 440x87x547mm
Enclosure / protection : steel-plastic / IP20
Environment
Safety : EN 62040-1-1 (EN 60950)
Electromagnetic compatibility : EN 62040-2
Ambient temperature : -10 to +40ºC
Audible noise at 1 meter : < 45 dB(A), load and temperature dependent
Max. relative humidity : 95% (non-condensing)