EasyManuals Logo
Home>Graham>Controller>Vari Speed S1000

Graham Vari Speed S1000 User Manual

Graham Vari Speed S1000
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
7
CONTROL SPECIFICATIONS
Service Factor 1.0
Form Factor 1.3 5
Duty Continuous
Overload Capability 150% for 1 minute
Speed Regulation 2% of Base Speed (for
95% Load Change)
Speed Range 50:1 @ Full Torque
Speed Potentiometer 5k ohm, 1W available accessory
Process Signal Input 0-5VDC or O-10VDC
(See Wiring and Warning on pg. 16)
Adjustments Minimum Speed (0-50%)
of motor base speed)
Maximum Speed (50
110% of motor base speed )
IR Compensation
(Adjustable from O to 25%
of rated output.)
Current Limit (10-150% of
Control Rating)
Acceleration (1/2 to 15
Seconds)
Deceleration (1/2 to 15
Seconds)