49
Duct Type Split Air Conditioner
Service Manual
FG(R)30/BNa-M FG(R)25/CNa-M, FG(R)40/BNa-M
4.3 Specication of Power Supply Wire and Air Switch
Model Power Supply Air Switch (A) Earthing section(mm
2
) Permit Min section (mm
2
)
FGR20/BNa-M(I) 380-415V 3N~ 50Hz 10 H05VV-F 1.5 H05VV-F 1.5
FGR25/CNa-M(I) 380-415V 3N~ 50Hz 10 H05VV-F 1.5 H05VV-F 1.5
FGR30/BNa-M(I) 380-415V 3N~ 50Hz 10 H05VV-F 1.5 H05VV-F 1.5
FGR40/BNa-M(I) 380-415V 3N~ 50Hz 10 H05VV-F 1.5 H05VV-F 1.5
FG20/BNa-M (I) 380-415V 3N~ 50Hz 10 H05VV-F 1.5 H05VV-F 1.5
FG25/CNa-M (I) 380-415V 3N~ 50Hz 10 H05VV-F 1.5 H05VV-F 1.5
FG30/BNa-M (I) 380-415V 3N~ 50Hz 10 H05VV-F 1.5 H05VV-F 1.5
FG40/BNa-M (I) 380-415V 3N~ 50Hz 10 H05VV-F 1.5 H05VV-F 1.5
FG(R)20/BNa-M (O) 380-415V 3N~ 50Hz 25 H05RN-F 4.0 H05RN-F 4.0
FG(R)25/CNa-M (O) 380-415V 3N~ 50Hz 32 H05RN-F 6.0 H05RN-F 6.0
FG(R)30/BNa-M (O) 380-415V 3N~ 50Hz 40 H05RN-F 10.0 H05RN-F 10.0
FG(R)40/BNa-M (O) 380-415V 3N~ 50Hz 40 H05RN-F 10.0 H05RN-F 10.0