Test Operation & Troubleshooting & Maintenance
72
1. Error List
There is no power supply.
Repower the unit when power supply is
available.
The power plug is loosened.
Replace the motor and check for the wiring
The volute or blade is deformed, or the
volute contacts the blade.
Replace the volute or the blade.
The air filter is clogged.
There are foreign matters at the
inlet/outlet or inside the duct.
There is abnormal noise from the motor.
The fastening screws are loosened.
The airflow rate is too
low.
The air filter is clogged.
There are foreign matters at the return
inlet and air outlet.
The duct resistance exceeds the design
value.
Lower the duct resistance or reselect the unit.
The cooling or
heating effect is poor.
The air filter is clogged.
The dampers are not opened.
The fins are clogged or damaged.
The entering water temperature cooling
is too high and too low for cooling.
Adjust the entering water temperature.
The condensate pipe is clogged.
The unit is not installed as required.
Adjust the unit and let the unit keep a certain
inclination degree.
The environmental air humidity is too
high.
Do humidification and do not let the
high-temperature and high-humidity air
coming into the room.
The fan stops but cold water is supplied
continuously.
Close the water dampers or run the unit.
The discharge valve is not tightened.
Tighten the discharge valve.