DC Inverter Multi VRF System
21
No
Debug item
Parameter name
Unit
Reference
7
Compressor’s
operating freq
Hz Changes in 10Hz~80Hz.
8
Compressor’s
operating current
A
When compressor works normally, the current is no
more than 18.4A.
9
Compressor’s IPM
temp
°C
When ambient temp is below 35°C(95°F), IPM temp
is lower than 80°C(176°F) and the highest temp
won’t be above 95°C(203°F).
10
Fan motor’s operating
freq
Hz Changes in 0~49Hz according to system’s pressure.
11
IDU
parameters
IDU ambient temp
°C(°F)
——
12
Indoor heat
exchanger’s inlet temp
°C(°F)
According to ambient temp, for a same IDU in
cool mode, the inlet temp will be 1°C~7°C
(34~45°F) lower than the outlet temp, and
4~9°C(39~48°F) higher than the low pressure
value.
For a same IDU in heat mode, the inlet temp will
be 10°C~20°C(50~68°F) lower than the outlet
temp.
13
Indoor heat
exchanger’s inlet temp
°C(°F)
14
Opening angle of
indoor EXV
PLS
In cool mode, the opening angle of indoor EXV
varies within 70~480PLS.
In heat mode, the opening angle of indoor EXV
varies within 70~480PLS.
15
Communication
parameters
Communication data
Number of IDUs detected by software is the same
with the actual number. No communication error.
16 Drainage system ——
Indoor unit can drain water out completely and
smoothly. Condensate pipe has no backward slope
of water; Water of outdoor unit can be drained
completely through drainage pipe. No water drop
from unit base.
17 Others ——
Compressor and indoor/outdoor fan motor do not
have strange noise. Unit can operate normally.
6 Common Malfunctions and Troubleshooting
(1) If there is abnormal condition (e.g. unpleasant smell), turn unit off and disconnect power immediately. Then
contact Gree authorized service center. If unit continues operation despite the abnormal condition, it may get
damaged and lead to electric shock or fire hazard.
(2) Do not repair the air conditioner by yourself. Improper maintenance may lead electric shock or fire hazard.
Please contact Gree authorized service center for maintenance.

Other manuals for Gree GMV-24WL/C-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-24WL/C-T and is the answer not in the manual?

Gree GMV-24WL/C-T Specifications

General IconGeneral
BrandGree
ModelGMV-24WL/C-T
CategoryInverter
LanguageEnglish

Related product manuals