(3).If the length between an IDU and its nearest branch is above 10m, then increase the size of the
liquid pipe of IDU (only for the pipe size that is≤6.35mm).
(4). If the height difference between indoor and outdoor units exceeds 90m, please consult the
manufacturer for specific technical requirements.