GMV DC Inverter VRF
61
Debugging Parameter Reference Value for DC Inverter VRF Unit
No.
Debugging item
Parameter name
Unit
Reference value
Remark
10
System
parameter
Outdoor
unit’s
parameter
Operation frequency of
inverter compressor
Hz ● Change among 20Hz~140Hz
11
IPM module
temperature of inverter
compressor
● IPM module temperature is lower than
80
. The highest temperature doesn’t
exceed 95
.
12
Drive bus voltage of
inverter compressor
V
● The normal bus voltage is 1.414 times of
the power supply voltage. For example, if
the three-phase power supply voltage is
390V, then the rectified bus voltage is:
390V×1.414 = 551V. The normal deviation
between the measured value and the
calculated value within 15V.
13
Fan operation
frequency
Hz
Adjust the operation in the range of
0~85Hz according to the system pressure
adjustment.
14
Indoor
units
parameter
Inlet tube temperature
of indoor heat
exchanger
According to the ambient temperature,
the inlet temperature is 1
~7
lower
than the outlet temperature for the same
indoor unit under cooling mode.
●The inlet temperature is 10
~20
lower than the outlet temperature for the
same indoor unit under the heating mode.
15
Outlet tube temperature
of indoor heat
exchanger
16
Opening of indoor
electronic expansion
valve
PLS
● 2000PLS electronic expansion valve: the
opening is adjusted automatically in the
range of 200~2000PLS;
● 480PLS electronic expansion valve: the
opening is adjusted automatically in the
range of 70~480PLS.
17
Drainage
system
● The indoor unit drains smoothly and
thoroughly, and the condensate water pipe
has no slope water storage; the outdoor
unit can drain water from the drain pipe
without dripping directly from the unit
foundation.
18
Other
●There is no abnormal noise for the
operation of the compressor, indoor fan
and outdoor fan. The unit is running
normally.
5 Operation Instruction
For instructions on how to use the air conditioner, please refer to the user manual of wired
controller or remote controller.

Other manuals for Gree GMV-950WM/G-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-950WM/G-X and is the answer not in the manual?

Gree GMV-950WM/G-X Specifications

General IconGeneral
BrandGree
ModelGMV-950WM/G-X
CategoryInverter
LanguageEnglish

Related product manuals