4.4.2 Panel installation
(1) Detach the panel’s Corner Cap, there is a mark “piping side” on one of the 4 corners, adjust
the panel direction so as to keep the mark and ttings on the same corner.
(2) Temporality hang the panel to body (there is four hangers on each corner of the panel, hang
the hangers to corresponding hooks on the body), as shown in g 4.4.4.
(3) Detach the air inlet grille from panel, make a wiring connection of signal receiver. Notices that
the connection wire not stuck in the middle of body and panel, or may cause air leakage and
lead to condensation water drop.
(4) Tighten 4 screws at each corner of panel respectively, x the panel on the body rmly.
(5) After tightening screws, reinstall the air inlet grille.
eiling
air outlet
⑤
decoration panel
5-8mm
.
indoor unit
sealing mate
4.5 Wired controller installation
Wired controller is optional accessory. If wired controller is needed, please contact your local
dealer and install the wired controller according to the instruction manual.
Notes:
Do perform the commissioning operation before rst use, automatic addressing or other settings,
please refer to the manual of ODU.