U-Match Series DC Inverter Service Manual
87
3.1.7.2 Additional Charge
Refrigerant suitable for a piping length of 5m is charged in the outdoor unit at the factory.
When the piping is longer than 7 m, additional charging is necessary.
For the additional amount, see Table 3-2-3.
Table 3-2-3
Unnecessary Charge
Pipe Length
Additional Refrigerant
Amount for Extra Pipe
When the height difference between the indoor unit and outdoor unit is larger than 10 meters, an oil
bend should be employed for every 6 meters.
Oil bend
Oil bend
Indoor
Outdoor
6m
Figure 3-2-5
3.2 Specification of Connection Pipe
Table 3-2-4
Size of Fitting Pipe(Inch)
Max. Height Difference
between Indoor Unit and
Outdoor Unit (m)
Drainage pipe(Outer
Diameter × wall thickness)
(mm)
The connection pipe should be insulated with proper water-proof insulating material.
The pipe wall thickness shall be 0.5-1.0 mm and the pipe wall shall be able to withstand the
pressure of 6.0 MPa. The longer the connecting pipe, the lower the cooling and heating effect performs.