cooling and heating effect performs.
3.4 Electrical Requirement
Electric Wire Size and Fuse Capacity.
Table 3.5
Notes:
①. The fuse is located on the main board.
②. Install the disconnect device with a contact gap of at least 3 mm in all poles
nearby the units (Both indoor unit and outdoor unit).The appliance must be
positioned so that the plug is accessible.
③. The specifications of the breaker and power cable listed in the Table above are
determined based on the maximum power (maximum amps) of the unit.
④. The specifications of the power cable listed in the Table above are applied to the
conduit-guarded multi-wire copper cable (like, YJV copper cable, consisting of PE
insulated wires and a PVC cable jacket) used at 40°С and resistible to 90°С (see
IEC 60364-5-52). If the working condition changes, they should be modified
according to the related national standard.
⑤. The specifications of the breaker listed in the Table above are applied to the
breaker with the working temperature at 40°С. If the working condition changes,