Harman® • P-Series Owner’s Manual_R1 • 03/1412 3-90-436168c
B. Fire Characteristics
Aproperlyadjustedrehasamediumactiveamepattern
that extends out of the burn pot approximately 6 inches
(152mm).
C. Feed Rate Adjustment Instructions
Thefeedadjustmentcontrolisfactorysetat#4,andshould
beadequateformostfuels.
However,iftheflameheightistoohighortoolow,youwill
needtoadjustthefeedrate.Waituntiltheappliancehasbeen
burningfor15minutesbeforemakingyouradjustmentsand
a
llow15minutesforfeedadjustmenttotakeeffect.
A. Starting Your First Fire
1. A room sensor is required for proper operation of this
appliance in “Room Temp” mode. At this time, ll the
hopper with pellets, insure the control is set to “OFF”.
Figure4.2.Plugthepowercordintoaproperlygrounded,
nearbyoutlet.
2.Oncepowerispresent,theunititwillrunthroughaquick
diagnosticstesttoinsurethecontrolisoperatingproperly.
Thisisnormal.
3. Foryourrstreitmaybenecessarytopurgetheauger
system by putting the feed limit knob to “Test” prior to
startingtheunit.Figure4.3.Thisinsuresthatplentyof
fuelenterstheburnpotforproperignition.
4. Fliptoggleswitchtodesiredmode“autoormanual”.Figure
4.4.Setfeedlimitknobtodesiredsettingandturnmode
dialto“RoomTemp”or“Constantburn”Figure4.5.Note:
Feedrateof#4isagoodstartingpoint.Adjustmentsmay
needtobemadedependingonfuelqualityand/orheat
outputdesired.
5.
Thefuelfeedsystemandtheignitershould
now
beon.
6. Oncetheappliancehasignited,letitburnforapproximately
7-10minutes.Afterthistime,theigniterlightshouldturn
offandtheunitshouldbegintooperateperthesettings
atthecontrol.
Figure 4.5
Odorsandvaporsreleasedduringinitialoperation.
• Curingofhightemperaturepaint.
• Openwindowsforaircirculation.
Odorsmaybeirritatingtosensitiveindividuals.
Figure 4.2 Figure 4.3
Figure 4.4
4
Operating Instructions
CAUTION