User Manual of HD-TVI Speed Dome
© Hikvision
respond to one alarm first and then respond to the next one after the user-defined interval. You
can set the on SEQUENCE submenu from 1 to 200 seconds.
3. Configure the alarm rest delay.
If there’s a linkage action has already been triggered by an alarm input, the speed dome will
only respond to the input from the same channel again after the user-defined reset delay time.
This is the rest time that the speed dome considers an alarm to be active when it’s physically
cleared. You can set the DELAY TIME from 0 to 300 seconds.
4. Resume the dome activity.
You can set ALARM RESUME to ON to enable the speed dome to resume its previous activity
after the triggered actions finished.
If the speed dome is moving when a linkage action is triggered, it will stop at the current
position and resume from this position after the linkage action finishes.
The speed dome can be configured to resume the PTZ positions, focus and iris value.
3.5.3 Configuring Alarm Output
Purpose:
An alarm output is a configurable alarm output interface on the speed dome back box which can
connect and trigger another alarm device to operate.
Steps:
1. Enter the alarm output configuration submenu:
MAIN MENUS > DOME SETTINGS > ALARM OUTPUT
ALARM OUTPUT
ALARM OUTPUT 1 CLOSE
DWELL TIME 2
ALARM OUTPUT 2 OPEN
DWELL TIME 0
BACK EXIT
Figure 3-21 Configure the Alarm Output
2. Click IRIS+ to edit the status of the alarm outputs. You can set the alarm output type as OPEN
(normally open) and CLOSE (normally closed).
There is 1 alarm output configurable; configuring the alarm output 2 will be invalid.
3. Move the cursor to DWELL TIME to set the duration of the alarm output signal. The configurable
rage is 0~60 seconds.
4. Link the alarm output to the configured alarm.