3 Capacity and selection data
YUTAKI M
TCGB0123 rev.2 - 10/2019
63
3
3.3.2 Maximum cooling capacity table (kW)
Ambient temperature (ºC WB)
10 15 20 25 30 35 40 45
System
Water
outlet
temp
(ºC)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
RASM-2VRE
22 7.40 0.95 7.80 6.93 1.03 6.74 6.45 1.11 5.83 5.98 1.19 5.04 5.50 1.26 4.35
18 7.50 0.96 7.80 7.10 0.97 7.30 6.80 1.08 6.30 6.40 1.21 5.30 5.75 1.27 4.54 5.10 1.32 3.85
15 7.00 0.97 7.20 6.92 0.99 7.02 6.83 1.00 6.84 6.75 1.01 6.67 6.27 1.10 5.68 5.79 1.19 4.84 5.31 1.29 4.13 4.83 1.38 3.50
10 6.80 0.97 7.00 6.58 1.01 6.54 6.37 1.04 6.12 6.15 1.08 5.72 5.71 1.17 4.86 5.26 1.27 4.14 4.82 1.37 3.52 4.37 1.47 2.98
7 6.20 0.98 6.30 6.10 1.03 5.94 6.00 1.07 5.60 5.80 1.12 5.20 5.40 1.23 4.40 5.00 1.33 3.75 4.55 1.43 3.19 4.10 1.52 2.70
5 5.50 1.08 5.10 5.20 1.17 4.46 4.90 1.26 3.90 4.60 1.34 3.42 4.30 1.43 3.00 4.00 1.52 2.63 3.70 1.61 2.30
RASM-3VRE
22 10.50 1.67 6.30 9.90 1.73 5.72 9.30 1.80 5.17 8.70 1.86 4.67 8.10 1.93 4.20
18 10.60 1.64 6.45 10.20 1.71 5.95 9.50 1.84 5.15 9.00 1.94 4.65 8.00 1.98 4.04 7.00 2.03 3.45
15 9.50 1.40 6.80 9.52 1.52 6.26 9.55 1.65 5.80 9.57 1.77 5.40 8.86 1.87 4.75 8.15 1.96 4.16 7.44 2.05 3.63 6.73 2.14 3.14
10 8.80 1.44 6.10 8.71 1.58 5.50 8.62 1.73 4.99 8.53 1.87 4.56 7.96 1.99 4.01 7.40 2.10 3.52 6.84 2.22 3.08 6.27 2.33 2.69
7 8.10 1.56 5.20 8.03 1.68 4.78 7.97 1.80 4.42 7.90 1.93 4.10 7.60 2.05 3.70 7.00 2.19 3.20 6.50 2.32 2.80 6.00 2.45 2.45
5 8.00 1.74 4.60 7.68 1.86 4.12 7.35 1.99 3.70 7.03 2.11 3.33 6.70 2.23 3.00 6.15 2.45 2.51 5.60 2.67 2.10
? NOTE
CAP: Capacity at compressor maximum frequency. Capacity is valid for difference between water inlet and water outlet of 3-8ºC.
IPT: Total input power.

Table of Contents

Other manuals for Hitachi RASM-2VRE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi RASM-2VRE and is the answer not in the manual?

Hitachi RASM-2VRE Specifications

General IconGeneral
BrandHitachi
ModelRASM-2VRE
CategoryHeat Pump
LanguageEnglish

Related product manuals