3 Capacity and selection data
YUTAKI M
TCGB0123 rev.2 - 10/2019
62
3.3 YUTAKI M
3.3.1 Maximum heating capacity table (kW) (Integrated)
Ambient temperature (ºC WB)
-20 -15 -10 -7 -2 2 7 12 15 20 25
System
Water
outlet
temp
(ºC)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
RASM-2VRE
60 3.20 2.29 3.64 2.25 4.00 2.22 5.00 2.17 5.50 1.77 5.66 1.71 5.93 1.61 6.20 1.51
55 4.00 2.42 4.20 2.27 4.48 2.25 4.70 2.24 6.00 2.22 6.30 1.80 6.46 1.68 6.73 1.48 7.00 1.27
50 4.36 2.32 4.60 2.22 4.85 2.13 5.05 2.05 6.15 2.01 6.65 1.71 6.85 1.61 7.17 1.43 7.50 1.25
45 4.00 2.35 4.25 2.30 4.72 2.22 5.00 2.17 5.22 2.00 5.40 1.86 6.30 1.80 7.00 1.63 7.23 1.54 7.62 1.38 8.00 1.23
40 4.15 2.34 4.54 2.24 4.93 2.14 5.17 2.08 5.32 1.86 5.45 1.70 6.40 1.59 7.25 1.48 7.48 1.42 7.87 1.31 8.25 1.21
35 4.30 2.32 4.50 2.14 5.02 2.04 5.33 1.98 5.42 1.73 5.49 1.53 6.50 1.38 7.50 1.34 7.73 1.30 8.12 1.24 8.50 1.18
30 4.50 2.23 4.80 2.09 5.31 1.93 5.62 1.83 5.69 1.65 5.75 1.50 6.70 1.34 7.75 1.30 7.98 1.27 8.37 1.20 8.75 1.14
25 4.70 2.14 5.10 2.04 5.60 1.82 5.90 1.68 5.95 1.56 6.00 1.46 6.90 1.30 8.00 1.27 8.23 1.23 8.62 1.16 9.00 1.09
20 4.90 2.04 5.40 1.99 5.89 1.71 6.18 1.54 6.22 1.48 6.25 1.43 7.10 1.26 8.25 1.24 8.48 1.19 8.87 1.12 9.25 1.05
RASM-3VRE
60 5.10 3.64 5.77 3.46 6.31 3.32 7.50 3.21 8.00 2.76 8.12 2.73 8.31 2.70 8.50 2.66
55 5.30 3.53 5.50 3.44 6.42 3.42 7.15 3.40 9.00 3.30 9.80 3.11 9.85 3.07 9.92 3.01 10.00 2.94
50 5.80 3.39 6.08 3.31 6.83 3.24 7.43 3.18
9.15 3.08 9.90 2.91 10.03 2.88 10.24
2.83 10.45 2.78
45 5.25 3.39 5.70 3.35 6.30 3.24 6.67 3.18 7.24 3.06 7.70 2.96
9.30 2.86 10.00 2.70 10.21 2.68 10.55
2.66 10.90 2.63
40 5.63 3.36 6.19 3.27 6.75 3.17 7.08 3.12 7.64 2.96 8.09 2.83
10.15 2.77 10.75 2.60 10.88 2.59 11.09
2.56 11.30 2.53
35 6.00 3.33 6.25 3.29 7.03 3.14 7.50 3.06 8.04 2.85 8.47 2.69
10.99 2.68 11.50 2.50 11.55 2.49 11.62
2.46 11.70 2.44
30 6.25 3.29 6.52 3.23 7.23 3.08 7.65 3.00 8.36 2.77 8.94 2.58
11.15 2.57 11.65 2.32 11.70 2.30 11.77
2.26 11.85 2.22
25 6.50 3.25 6.80 3.16 7.42 3.02 7.80 2.94 8.69 2.68 9.40 2.48
11.30 2.46 11.80 2.15 11.85 2.11 11.92
2.06 12.00 2.00
20 6.75 3.21 7.08 3.10 7.62 2.97 7.94 2.88 9.09 2.62
10.00
2.40
11.50 2.40 12.00 2.00 12.16 1.97 12.43
1.92 12.70 1.87
? NOTE
CAP: Capacity at maximum compressor frequency (kW). Capacity is valid for difference between water inlet and water outlet of 3-8 ºC.
IPT: Total input power (kW)
The table above shows the input power (IPT) at maximum capacity (CAP). Most of the time, the unit runs at partial load, so that the actual
input is lower.

Table of Contents

Other manuals for Hitachi RASM-3VRE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi RASM-3VRE and is the answer not in the manual?

Hitachi RASM-3VRE Specifications

General IconGeneral
BrandHitachi
ModelRASM-3VRE
CategoryHeat Pump
LanguageEnglish

Related product manuals