Honeywell DBC2000E10 Series Installation Instructions

Honeywell DBC2000E10 Series
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
ENI7003R8 KO65 2013
2
3. SPECIFICATIONS
Table 1: Model Selection Guide
Model
Description / Application Supply voltage
DBC2000E10xx (*) Standard model
115V or 230V
(see detailed specs on page 4)
DBC2000E20xx (*) Enhanced model
DBC2000E30xx (*) Ultimate model (future release)
The Enhanced Model includes a Valve Proofing System.
The Ultimate model includes both remote bus communication and a Valve Proofing System.
(*) xx depends on supply voltage and timings. For exact model number, please refer to product selection matrix ot
technical catalogue on http://products.ecc.emea.honeywell.com/europe.
Table 2: Sequence timing Standard Model
Waiting for
AFS
Waiting for
HF
Pre-
purge
Ignition
Pilot-
only
Main
trial
Main
stabilization
Post-
purge
Flame
failure
response
300s (max)
300s (max) 35s
1)
3s 5s
3s
2)
4s
2)
15s
3)
1s (max)
1)
Default pre-purge time is 35s. Other timings on request, by OS number selection.
2)
Set to 0s. when DBI function is enabled (terminal 22 jumpered to line voltage).
3)
Set to 0s. when “no post-purge” feature is enabled (terminal 12 jumpered to line voltage).
Sequence at flame failure: immediate lock out
Table 2a: Sequence timing Enhanced and Ultimate Models
Waiting for
AFS
Waiting for
HF
Pre-
purge
Ignition
Pilot-
only
Main
trial
Main
stabilization
Post-
purge
Flame
failure
response
300s (max)
300s (max) 35s
1)
3s 5s
3s
2)
4s
2)
15s
3)
1s (max)
1)
Default pre-purge time is 35s. Other timings on request, by OS number selection.
2)
Set to 0s. when DBI function is enabled using the DIP-switches on the front, at the bottom left corner (Fig 4-5).
3)
Set to 0s. when “no post-purge” feature is enabled using the DIP-switches on the front, at the bottom left corner (Fig 4-5).
Sequence at flame failure: immediate lock out
Table 3: Contact ratings
Terminal
Load Contact rating
3 Blower / Fan 3A @ cosφ=0.6
4 Ignition transformer 3A @ cosφ=0.6
5 Intermittent pilot or main (DBI) valves 3A @ cosφ=0.6
6 Interrupted pilot 3A @ cosφ=0.6
7 Main (PI) valves 3A @ cosφ=0.6
12 Main (PI) valve 2 (ENH/ULT models only) 3A @ cosφ=0.6
8, 9, 10, 11 Control motor 0.5A @ cosφ=0.6
21 Alarm 0.5A @ cosφ=0.6
Total load (based on set): Max 8A (Internal Fuse : 10A)
Total load (based on terminal 4,5,6,7): Max 5A (Internal Fuse : 6.3A)

Other manuals for Honeywell DBC2000E10 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell DBC2000E10 Series and is the answer not in the manual?

Honeywell DBC2000E10 Series Specifications

General IconGeneral
BrandHoneywell
ModelDBC2000E10 Series
CategoryController
LanguageEnglish

Related product manuals