EasyManuals Logo
Home>Honeywell>Thermostat>DT92E1000

Honeywell DT92E1000 User Manual

Honeywell DT92E1000
17 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
DT92 WIRELESS DIGITAL ROOM THERMOSTAT
15
INSTALLER MODE – HOW TO SET PARAMETERS
Each parameter is identified by a 2-letter code, and has a range of values. These are shown in the table below,
followed by instructions on how to enter Installer Mode, how to select a parameter and change its value, and finally
how to exit Installer Mode.
Description Parameter Range of values Factory (default) value
Minimum ON/OFF time Ot 1, 2, 3, 4, 5 minutes 1 minute
Cycle rate Cr 3, 6, 9, 12 cycles/hour 6
Proportional band width Pb 1.5 to 3.0°C 1.5°C
Temperature measurement offset tO -3 to 3°C 0
Upper setpoint limit uL 21 to 35°C 35°C
Lower setpoint limit LL 5 to 21°C 5°C
Energy saving ECO temperature
(this parameter is only available on
the DT92E model)
ES 5 to 35°C 18°C
Selection of heat/cool changeover HC 0 = disable
1 = enable
0
* Off/standby setpoint OS -- = off,
5 to 16°C
5°C
** Room temperature sensor use Su 0 = DT92 alone
1 = DT92 with HR80, using
HR80 sensors
2 = DT92 with HR80, using
DT92 sensor
0
Failsafe mode (loss of RF
communications)
LC 0 = switch OFF
1 = operate at 20% ON
0
** Enable HR80 window-open
function
H0 0 = disable
1 = enable
0
** Enable HR80 local override HL 0 = disable
1 = enable
1
Reset parameters FS 0, 1 1 (factory settings)
* In cooling mode the off/standby setpoint defaults to OFF
** Only required if system contains HR80 programmable radiator valves
Specific Applications Setting What requires to be changed?
Cycle
s/
hour
Minimum
on/off time
Gas boilers
(<30kW)
6 1 No changes required
Oil boiler 3 4 1. Set minimum ON/OFF time to 4 minutes
2. Set cycle rate to 3 cycles/hour
Thermal actuator 12 1 Set cycle rate to 12 cycles/hour
Heating
Zone valve
6 1 No changes required
1. Configure the thermostat to allow switching between
heating and cooling modes (set parameter HC = 1)
2. Set the thermostat to the required mode of operation
(heating or cooling) by pressing the and
buttons together for 3 seconds when in normal run
mode (does not work in off/standby mode).
Heatpump / Air
conditioner
3 4 1. Set minimum ON/OFF time to 4 minutes
2. Set cycle rate to 3 cycles/hour
Air
conditionin
g
Fan-coil unit 6 1 No changes required
Some parameters require to be set to match specific applications. Recommended settings are shown in the table
below.

Other manuals for Honeywell DT92E1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell DT92E1000 and is the answer not in the manual?

Honeywell DT92E1000 Specifications

General IconGeneral
BrandHoneywell
ModelDT92E1000
CategoryThermostat
LanguageEnglish

Related product manuals