EasyManuals Logo
Home>Honeywell>Security System>LYNXR

Honeywell LYNXR User Manual

Honeywell LYNXR
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
–11–
Installing Wireless Zones
General Information
Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16
wireless buttons.
Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal
range of 200 feet.
Transmitters: 5800 Series transmitters have built-in serial numbers that must be entered into the
system using the 56 or 83 interactive mode, or input to the control via the downloader. 5800
Series transmitters (except the 5800RL, which is described separately) do not have DIP switches.
Each transmitter's zone number is programmed into the system in 56 mode. Some transmitters,
such as the 5816 and 5817, can support more than one "zone" (referred to as loops or inputs). On the
5816, for example, the wire connection terminal block is loop 1,the reed contact is loop 2. Each loop
must be assigned a different zone number.
U
L
The 5816 and 5817 Transmitters do not have EOL supervision of their loop wiring. Therefore, for
UL Household Burglary installations, the loop wiring may not exceed 3 feet.
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP,
5819, 5819S(WHS & BRS), 5828/5828V and 5850(GBD) transmitters are not intended for any UL
installations.
For button transmitters (RF "keys") such as the 5804 and 5801, you must assign a unique zone
number to each individual button used on the transmitter. Each button on the transmitter also has
a pre-designated loop or input number, which is automatically displayed.
House Identification
If you are using a 5804BD/5804BDV Wireless Keypad with the system, you must program a House
ID Code (01–31) in field 24 to establish proper communication, and the keypad must be set to the
same ID. House ID 00 disables all wireless keypads. An RF House ID is not necessary for other 5800
Series transmitters; the entry should be left at “00” (default) in those cases.
Transmitter Supervision
Except for some transmitters/keypads that may be carried off-premises (5804, 5804BD, 5804BDV,
5804E, and 5804WATCH), each transmitter is supervised by a check-in signal that is sent to the
receiver at 70–90 minute intervals. If at least one check-in is not received from each supervised
transmitter within a 12-hour period, the "missing" transmitter number(s) and "FAULT" will be
displayed. The supervision for a particular transmitter in the system that may also be carried off
the premises (5801, 5802MN) may be turned off by entering it as a "UR" (unsupervised RF) type, as
described in the 56 Enhanced Zone Programming Mode section.
5800 Series transmitters have built-in tamper protection and will annunciate as a fault condition if
covers are removed.
Transmitter Input Types
Each of the following transmitters has one or more unique factory-assigned input (loop) ID codes.
Each of the inputs requires a programming zone
(e.g., a 5804's four inputs require four button zones).
Transmitters can be entered as one of the following types
(see transmitter’s instructions for appropriate
input type)
:
Type Description
"RF" (Supervised RF) Sends periodic check-in signals, as well as fault, restore, and low battery
signals. The transmitter must remain within the receiver's range.
"UR" (Unsupervised RF) Sends all the signals that the "RF" type does, but the control does not
supervise the check-in signals. The transmitter may therefore be carried
off-premises.
"BR" (Unsupervised Button RF) These only send fault signals. They do not send low battery signals until
they are activated. The transmitter may be carried off-premises.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM

Table of Contents

Other manuals for Honeywell LYNXR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell LYNXR and is the answer not in the manual?

Honeywell LYNXR Specifications

General IconGeneral
BrandHoneywell
ModelLYNXR
CategorySecurity System
LanguageEnglish

Related product manuals