RM7890, RM7895 100 Vac
FEATURES
Safety features:
Closed loop logic test.
Dynamic AMPLI-CHECK™ circuitry.
Dynamic input check.
Dynamic safety relay test.
Dynamic self-check logic.
Expanded safe-start check.
Internal hardware status monitoring.
Tamper resistant timing and logic.
Access for external electrical voltage checks. Application
exibility.
Dependable, long-term operation provided by microcom-
puter technology.
Five light emitting diodes (LEDs) for sequence informa-
tion.
Interchangeable type plug-in flame amplifiers.
Nonvolatile memory retains history files and sequencing
status after loss of power.
Selectable relight or lockout on loss of flame.
OPTIONAL FEATURES
Communication interface capability.
First-out annunciation and system diagnosis are provided
by a two-row by 20-column display located on the option-
al keyboard display module (KDM).
Local or remote annunciation operation and fault informa-
tion.
Remote reset.
Burner controller data using S7800 Keyboard Display:
Flame signal strength.
Hold status.
Lockout/alarm status.
Sequence status.
Sequence time.
Total cycles of operation.
Total hours of operation.
Fault history providing the six most recent faults:
Cycles of operation at the time of the fault.
Fault message and code.
Hours of operation at the time of the fault.
Sequence status at the time of the fault.
Sequence time at the time of the fault.
Diagnostic information:
Device type.
Flame amplifier type.
Flame failure response time. Manufacturing code.
On/Off status of all digital inputs and outputs.
Software revision and version of RM7890/ RM7895
and optional Keyboard Display Module.
Status of configuration jumpers.
SPECIFICATIONS
Electrical Ratings:
See Table 2.
Voltage and Frequency:
100 Vac (+10/-15%), 50/60 Hz (± 10%).
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A maximum, type SC or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to 60°C).
Storage: -60°F to 150°F (-51°C to 66°C).
Humidity: 85% relative humidity continuous, noncondensing.
Vibration: 0.5G environment.
Dimensions:
See Fig. 1 and 2.
Weight:
RM7890, RM7895 with Dust Cover: 1 lb, 13 oz (829 grams)
unpacked.
Approvals:
cULus Underwriters Laboratories Inc. Listed: File No. MP268.
ANSI/UL 60730-2-5 / CSA C22.2 No. 60730-2-5 -
Automatic Electrical Controls for Household and Similar
Use, Part 2-5: Particular Requirements for Automatic
Electrical Burner Control Systems.
FM: Factory Mutual Approved: Report No. 1V9A0.AF.
EAC: TC N RU д-US.Aи3O.B.04013
Exida: IEC/EN 61508:2010 Parts 1-7, SIL 3 capable.
FCC Federal Communications Commission: Part 15, Class B,
Emissions.
Swiss Re (formerly Industrial Risk Insurers): Acceptable.
Mounting:
Q7800A Wiring Subbase for panel mounting.
Q7800B Wiring Subbase for wall or burner mounting.
Required Components:
Plug-in Flame Signal Amplifier (See Table 4).
ST7800A Purge Timer (for RM7895 only).
Accessories:
Keyboard Display Modules (KDM)
S7800A1142 2-Line VFD Keyboard Display Module
S7800A2142 4-line LCD keyboard display module
Communications
Modbus using S7810M1003 Modbus Module
or
configuring the S7800 Keyboard Display.
S7810A1009 Data ControlBus™ Module (if no KDM used).
Miscellaneous
A7800A1002 7800 SERIES Tester
S7820A1007 Remote Reset Module
203541 Data ControlBus Connector, 5-wire
203765 Remote Display Mounting Bracket
221729 Dust Cover, Relay Module
32-00216-01 2

Questions and Answers: