RM7890, RM7895 100 Vac
Table 5. Flame Detection Systems.
Plug-in Flame Signal Amplifiers Applicable Flame Detectors
Type Color Self-Checking Model Flame Failure
Response
Time
a
Fuel Type Models
Rectification
Green No R78 47A
e
0.8 or 3.0 sec. Gas Rectifying
Flame Rod
Holders
f
C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179
No R78 47A
e
3.0 sec Gas, oil,
coal
Ultraviolet
(Purple
Peeper®)
C7012A,C
Dynamic
AMPLI-CHECK®
R7847B
c,e
0.8 or 3.0 sec Gas Rectifying
Flame Rod
Holders
f
C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179
Dynamic
Ampli-Check®
R7847B
c,e
3.0 sec Gas, oil,
coal
Ultraviolet
(Purple
Peeper®)
C7012A,C
Infrared Red/
White
No R7852A 3.0 sec. Gas, oil,
coal
Infrared
(Lead
Sulde)
C7915
Dynamic
AMPLI-CHECK®
R7852B
c
Ultraviolet Purple No R7849A 0.8 or 3.0 sec Gas, oil Ultraviolet
(Minipeeper)
C7027, C7035, C7044
d
Dynamic
Ampli-Check®
R7849B
c
0.8 or 3.0 sec Gas, oil Ultraviolet
(Minipeeper)
C7027, C7035, C7044
d
Dynamic
Self-Check
R7861A
b
0.8 or 3.0 sec Gas, oil,
coal
Ultraviolet C7061
Blue Dynamic
Self-Check
R7886A,M
b
3.0 sec Gas, oil,
coal
Ultraviolet
(Adjustable
Sensitivity)
C7076
Optical White Dynamic
Ampli-Check®
R7851B 0.8 or 3.0 sec Gas, oil,
coal
Optical (UV,
Visible Light)
C7927, C7962
Dynamic
Self-Check
R7851C
b
3.0 sec Gas, oil,
coal
Optical (UV
only)
C7961
a
Flame Failure Response Time (FFRT) depends on selection of amplifier.
b
Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner operation and
shuts down burner if detection system fails.
c
Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.
d
Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use C7061A,M
Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A Amplifier as ultraviolet flame detection system for
appliances with burners that remain on continuously for twenty-four hours or longer.
e
R7847A,B Amplifiers with 0.8 second FFRT should NOT be used with C7012A,C Solid State Ultraviolet Detectors.
f
Order flame rod separately, see flame detector Instructions for holder.
5 32-00216-01