4 32-00006—03
Safety Features
• Class C operating software system
• Fail-safe feedback
• Curve verification algorithms
• Password protected
• Built in self test
• No slope constraints that would limit the steepness of the
curve
• Component anti-swap protection
• Off curve checking algorithm
Specifications
Electrical Ratings
Voltage and Frequency: See Tables 1–5.
Environmental Ratings:
Ambient Temperature:
Operating: -20°F to +150°F (-29°C to +66°C).
Shipping: -40°F to +150°F (-40°C to +66°C).
Humidity: 95% continuous, noncondensing.
Vibration: 0.5G environment
Dimensions: See Fig. 1.
Weight: 13.6 oz (0.39 Kg)
Approvals
Underwriters Laboratories Inc. Listed, File: MP268
Factory Mutual
IRI Acceptable
Federal Communications Commission: Part 15, Class A
Must be mounted inside a grounded metal enclosure.
Mounting: DIN Rail (See Fig. 2)
Required Components
R8001A1001 SLATE Base Module
R8001S9001 Sub-Base Module