XNX Relay Board Installation Guide
3
1 Relay Option Board
The relay option (XNX-Relay) provides 3 form “C” contacts for alarm and fault indication. A remote
reset is provided to silence alarms.
Note
This option is not available with the Modbus
®
or Foundation Fieldbus
TM
options.
Wiring for the relays is through an available cable/conduit entry to terminal block TB3.
Warning: Power
externally supplied.
Disconnect at source
prior to servicing.
3-5
3-4
3-3
3-2
3-1
3-6
3-7
3-8
3-9
C
NC
TB4
Remote
Reset SW
Relay Ratings
250VAC 5A
24VDC 5A
NO
C
NC
NO
NC
C
NO
Fault Level 2 Level 1
TB-3 RELAY
TB3 Relay Connections
Warning: Power externally
supplied, disconnect at source
prior to servicing
Relay Contact Ratings:
250 VAC 5 amps
24 VDC 5 amps
Relay
TB3
1 NC
2 C
3 NO
4 NC
5 C
6 NO
7 NC
8 C
9 NO
TB4
1 1
2 2
1
2
3
4
5
6
7
8
9
TB3
1
2
TB4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX Universal Transmitter and is the answer not in the manual?

Honeywell XNX Universal Transmitter Specifications

General IconGeneral
BrandHoneywell
ModelXNX Universal Transmitter
CategoryTransmitter
LanguageEnglish

Related product manuals