Unit Dimensions
(HxWxD)
5 5 in (12.7 cm) x 17.2 in (43.7 cm) x 29.3 in (74.4 cm)
Shipping Dimensions
(HxWxD)
14.4 in ( 36.58 cm) x 23.6 in ( 60 cm) x 38.78 in ( 98.5 cm)
Unit Weight
126 lbs (57kg)
Shipping Weight
192 lbs ( 87 kg)
BTU Break Down
BTU On Line
478 all models
BTU On Battery
1041
Battery String Voltage
216V
Battery Type
12V 27W
Battery Quantity
18
Electrical Input
Voltage Range
160-253V at 200/208V nominal; 176-253V at 220, 230, and 240V nominal
Frequency
50/60 Hz
Input Plug
L6-30P, 3m cord
Online Efficiency
94%
REPO
Remote Emergency Power-Off disables AC power to load
Electrical Output
Online Regulation
-10% to +6% of nominal voltage
On battery Regulation
±5% of nominal voltage
Voltage Wave Form
Sine wave
Connections
See Model Selection Matrix; divided into 2 Load Segments
Output Protection
Re-settable circuit protectors
Battery
Type
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Extended Batteries
Up to four ERMs supported
Backup Time
See Backup Times Chart
Recharge Time
<3 hours to 80% usable capacity; <48 hours for complete recharge
Battery String Voltage
216V
Battery Type
12V 27W
Battery Quantity
18
Communications
LED Indicators
LCD and switch membrane integrated into the front panel; with five-button
control (four buttons for UPS power control and one button under the front
bezel for configuration).
Environmental and Safety
Operating Temperature
50° to 104° F (10° to 40° C )
Transit Temperature
-13° to 131° F (-25° to 55° C)
Storage Temperature
32° to 77° F (0° to 25° C )
Operating Humidity
20% to 80% (non-condensing)
Storage Humidity
5% to 95%
Operating Altitude
Up to 6,60 ft (2000 m) above sea level
Transit Altitude
49,000 ft (15,000 m) above sea level
Audible Noise
<45db (in normal operation)
QuickSpecs
R5000 Uninterruptible Power System (UPS)
Technical Specifications
DA - 14109 North America — Version 5 — November 1, 2013
Page 10