Specifications 50
Specifications
UPS physical specifications
Parameter Value
Height
17.1 cm (6.75 in)
Depth
Width
43.7 cm (17.2 in)
Weight
75 kg (165 lb)
Ambient operation
0~40°C
ERM physical specifications
Parameter Value
Height
12.7 cm (5 in)
Depth
71.9 cm (28.3 in)
Width
43.8 cm (17.24 in)
Weight
UPS input specifications
NOTE: An asterisk (*) indicates the default setting.
UPS model Utility voltage
frequency (Hz)
Available settings
utility voltage (VAC)
Dedicated
branch circuit
rating (A)
Line cord
R7000 NA/JPN
50/60 200/208*/220/230/
240
40
50 low input
Nondetachable power
cord with NEMA
CS8265C plug
R7000 INTL
50/60 200/208/220/230*/
240
32 Nondetachable power
cord with 32 A IEC-309
plug
UPS output specifications
UPS model Load
segment
Circuit
breaker
Output receptacles Maximum current
R7000 NA/JPN
1 20 A¹ 2 x IEC-320-C19 16 A per receptacle²
2 x IEC-320-C13 10 A per receptacle