TP48200A-DX12A1 Telecom Power
User Manual
Copyright © Huawei Technologies Co., Ltd.
3.2 Power Distribution Unit
Table 3-1 Power distribution specifications
AC input: two 3-pole 40 A circuit breakers, with a knob-type dual
power switch
AC output: one German standard socket (with a 10 A RCD), one
1-pole 10 A circuit breaker, and AC light power terminals and one
time relay (5 A resistive load or 1 A capacitive load)
BLVD circuit breakers: 2x32 A/1P, 2x20 A/1P, 2x16 A/1P, 2x10
A/1P, 2x6 A/1P
LLVD circuit breakers: 3x63 A/1P
One 2-pole 125 A circuit breaker
3.3 Rectifier
Rectifiers convert AC input into stable DC output.
Figure 3-5 Rectifier
Table 3-2 Rectifier indicator description
The rectifier has an AC power input.