HHT-5000/6000/8000/10000/12000 USER MANUAL 14
5.3.2 Back-up Switch Types
Please install an individual 2-stage miniature circuit breaker according to the following
specifications.
5.4 PV Wire Assembly and Connection
1. PV modules of the connected strings must be of: the same time, identical alignment
and tilting angle.
2. Before commissioning and connecting the PV arrays, the DC switch MUST be open.
3. Parallel strings must have the same number of modules.
4. It is mandatory to use the DC connectors within package for the connection of PV
arrays.
5. The polarity of the PV arrays MUST be compatible to the DC connectors of the
inverter.
6. The DC input voltage AND DC input current of the PV array MUST never exceed the
maximum input allowance of the inverter.
Model
Maximum Back-up current
A
Back-up Breaker Rated current
A
HHT -5000
17
50A/230V AC
HHT -6000
20
50A/230V AC
HHT -8000
22
63A/230V AC
HHT -10000
22
63A/230V AC
HHT-12000
23
63A/230V AC