HHT-5000/6000/8000/10000/12000 USER MANUAL 32
Bus-voltage is 20V lower
than standard Bus-voltage
Check the open-circuit voltages of the strings and make sure it is
below the maximum DC input voltage of the inverter. If the input
voltage lies within the permissible range while the fault occurs,
please contact the service.
Check the connection of DRM device. If the DRM device is
connected normally while this fault occurs, please contact the
service.
Check the connection of DRM device. If the DRM device is
connected normally while this fault occurs, please contact the
service.
N and PE voltage
exceeds permitted
range
Voltage between N and PE is
over limit
Check if the inverter is securely grounded.
Bus voltage is over limit
Disconnect the inverter from the utility grid and the PV array, and
reconnect it after LED turns off. If this fault is still being displayed,
please contact the service.
Battery BMS communication
interrupted
Check the connection of BMS cable with storage inverter. If the
BMS cable is connected normally while this fault occurs, please
contact the service.
Current transducer not
connected
Check the connection of CT device. If the CT device is connected
normally while this fault occurs, please contact the service.
Current transducer reverse
connection
Try to change the direction of CT device. If the CT device is
connected correctly while this fault occurs, please contact the
service.
Check the connection of battery. If the battery is connected
normally while this fault occurs, please contact the service.