INSTALLATION AND OPERATION INSTRUCTIONS
12
IBC INDIRECT WATER HEATERS - ALL MODELS
7) - Troubleshooting
6. Using a funnel, pour one gallon of commercial ice maker cleaning solution
into the tank through the relief valve opening. Follow the instructions,
cautions, and warnings supplied with the cleaning solution.
7. Turn on the power to the boiler and water heater, program the IBC control
to its highest DHW temp. setting, and allow the boiler to heat the water until
the control is satised. If the boiler control is not satised after 45 minutes
of operation, program the IBC DHW control setting to its lowest temp.
8. Allow the heated solution to set in the tank 30 minutes.
9. Drain the tank completely using ttings and hoses, as required, to reach a
drain.
10. Fill the water heater tank with fresh, cold, water and drain it completely.
Repeat lling and draining at least three (3) times to ush all of the
cleaning solution from the tank.
11. Reinstall the relief valve and the drain piping.
12. Open the cold water supply and ll the tank with water. Purge the air from
the tank and the piping by opening the cold and hot water faucets in the
house.
13. Return the IBC DHW control setting to the temperature noted in Step 2.
SYMPTOM DIAGNOSIS REMEDY
WATER AT FAUCETS TOO
HOT
IBC boiler DHW
temperature setting
too high
Reduce the DHW Tank Set Point
temperature in the Congure Load Menu
DHW temperature
sensor problems
giving false reading to
IBC Control
Sensor has fallen from well
Sensor giving incorrect resistance reading
sensor connected to Therm terminals
instead of DHW S terminals
improper 3rd party sensor installed in well
WATER AT FAUCETS TOO
COOL
IBC boiler DHW
temperature setting
too low
Increase the DHW Tank Set Point
temperature in the Congure Load Menu
IBC boiler DHW
Maximum Supply
Temp. setting too low
Make sure the Maximum Supply Temp.
setting is at least 10°F higher than the DHW
Supply Setpoint PLUS 1/2 of the Supply
Diff’l Temp setting.