EasyManuals Logo
Home>IBC>Boiler>EX 850

IBC EX 850 User Manual

IBC EX 850
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
8.4.1 Ignition issues
Ignition issues
Issue Diagnosis Fix
Noisy spark when igniting Ignition lead is not firmly
connected.
Reconnect ignition lead.
Contaminants/moisture on
igniter probe/flame sensor.
Ensure probe is dry by re-running
post-purge; otherwise, clean or
replace igniter probe.
Boiler rumbles when
igniting.
Fluctuating gas pressure/
gas pressure too high/too
low.
Check CO
2
level via analyzer.
Check for proper gas piping Check pressure with manometer
during ignition.
Boiler will not attempt to
ignite. Fan and pump are
operating normally.
No power to ignition control
module.
Check system wiring.
Check air reference tubing.
Igniter probe/flame sensor
disconnected.
Reconnect probe.
Defective Control Module. Check ignition output from control
module.
Boiler will not attempt to
ignite. Fan and / or pump are
off Display not illuminated
No power to boiler. Check line voltage.
Defective transformer. Check transformer. Reconnect or
replace as needed.
8.4.1 Ignition issues

Table of Contents

Other manuals for IBC EX 850

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBC EX 850 and is the answer not in the manual?

IBC EX 850 Specifications

General IconGeneral
BrandIBC
ModelEX 850
CategoryBoiler
LanguageEnglish

Related product manuals