Hardware specications provide detailed information for your rack, including dimensions, electrical,
power, temperature, environment, and service clearances.
7014-T00 and 7014-T42 rack weight distribution and floor loading
Racks can be heavy when populated with several drawers. Use the Weight distribution distances for racks
when loaded and Floor loading for racks when loaded tables to ensure proper floor loading and weight
distribution.
The 7014-T00 and 7014-T42 racks can be heavy when several drawers are present. The following table
shows the necessary weight distribution distances for the 7014-T00 and 7014-T42 racks when loaded.
Table 43. Weight distribution distances for racks when loaded
Rack System
weight
1
Width
2
Depth
2
Weight distribution distance
3
Front and back Left and right
7014-T00
4
816 kg
(1795 lb)
623 mm
(24.5 in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
467.4 mm (18.4 in)
7014-T00
5
816 kg
(1795 lb)
623 mm
(24.5 in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
0
7014-T00
6
816 kg
(1795 lb)
623 mm
(24.5 in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
559 mm (22 in)
7014-T42
4
930 kg
(2045 lb)
623 mm
(24.5 in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
467.4 mm (18.4 in)
7014-T42
5
930 kg
(2045 lb)
623 mm
(24.5 in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
0
7014-T42
6
930 kg
(2045 lb)
623 mm
(24.5 in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
686 mm (27 in)
Notes:
1. Maximum weight of fully populated rack, units are lb with kg in parentheses.
2. Dimensions without covers, units are mm with inches in parentheses.
3. The weight distribution distance in all four directions is the area around the rack perimeter (minus covers)
necessary to distribute the weight beyond the perimeter of the rack. Weight distribution areas cannot
overlap with adjacent computer equipment weight distribution areas. Units are inches with mm in
parentheses.
4. Weight distribution distance is 1/2 the service clearance values that are shown in the gure plus cover
thickness.
5. No left and right weight distribution distance.
6. Left and right weight distribution distance that is required for a 70 lb/ft
2
raised floor loading objective.
The following table shows the necessary floor loading for the 7014-T00 and 7014-T42 racks when
loaded.
Table 44. Floor loading for racks when loaded
Rack Floor loading
Raised kg/m
1
Non-raised kg/m
1
Raised lb/ft
1
Non-raised lb/ft
1
7014-T00
2
366.7 322.7 75 66
7014-T00
3
734.5 690.6 150.4 141.4
7014-T00
4
341 297 70 61
Site and hardware planning 37